प्रशीतन प्रणाली की पाँच सामान्य समस्याएं
सबसे पहले, अपर्याप्त सर्द का उपचार
1. विफलता घटना: पूरी मशीन का शीतलन प्रभाव खराब है, पानी का आउटलेट केवल थोड़ा ठंडा है, और उच्च - दबाव पक्ष और निम्न - दबाव पक्ष पर दबाव पाया जाता है कई गुना दबाव गेज के साथ कम हो (कंप्रेसर की सामान्य गति के तहत, जब परिवेश का तापमान लगभग 35 ℃ होता है, तो निम्न दबाव मीटर सूचकांक 1kg / cm2 से कम होता है, उच्च - दबाव मीटर सूचकांक कम होता है 10 किग्रा / सेमी 2) की तुलना में, और बुलबुले के प्रवाह को दृष्टि ग्लास से देखा जा सकता है।
2. The cause of the failure: the refrigeration system has a refrigerant leakage point, which results in insufficient refrigerant.
3. Treatment method: 1). Use electronic leak detector to find the leak point and repair or replace parts.
2). If the parts are not replaced, only the appropriate amount of refrigerant can be added; if the parts are replaced, the appropriate amount of refrigeration oil should be added as required, and the refrigerant should be added after the system is evacuated.
दूसरा, रेफ्रिजरेंट का ओवरचार्ज
1. Failure phenomenon:
शीतलन प्रभाव खराब है, और उच्च - दबाव पक्ष और निम्न - दबाव का दबाव कई गुना अधिक है जब कई गुना दबाव गेज (जब कंप्रेसर की गति सामान्य है और परिवेश का तापमान है) 35 ° C है, उच्च - दबाव नापने का यंत्र दबाव लगभग 19 किलो / सेमी 2 है, और निम्न - दबाव नापने का यंत्र 2.3 किलो / सेमी 2 है, और दृष्टि कांच में कोई हवाई बुलबुले नहीं देखा जा सकता है ।
2. Failure reason: Too much refrigerant is added in the refrigeration system, so that the refrigeration capacity cannot be fully exerted, resulting in poor refrigeration effect.
3. Treatment method: Connect the manifold pressure gauge to the system, and slowly loosen the manual valve on the low pressure side of the manifold pressure gauge, so that the refrigerant is slowly discharged (cannot be discharged from the high pressure side, because the refrigerant will be taken out from the high pressure side) A large amount of freezing oil) until the pressure on the high and low sides is normal, and the refrigerant flows clearly from the sight glass, and occasionally bubbles flow through.
तीसरा, शीतलन प्रणाली को हवा के साथ मिलाया जाता है
1. विफलता घटना: पूरी मशीन की शीतलन क्षमता कम हो जाती है; उच्च दाब पक्ष पर दबाव कई गुना अधिक पाया जाता है जब कई गुना दबाव नापने का यंत्र चेक किया जाता है, और निम्न दाब पक्ष पर दबाव कभी-कभी सामान्य मान से अधिक हो सकता है (कंप्रेसर की गति सामान्य है और परिवेश का तापमान 35 ° C है इस समय, उच्च - दबाव का दबाव 20kg / cm2 से अधिक है, और उच्च - का सूचक दबाव मीटर दोलन कर रहा है; दूसरी ओर, कई बुलबुले बहते देखे जा सकते हैं; दृष्टि कांच से।
2. Reasons for failure:
सिस्टम में हवा मिलाई जाती है। मुख्य रूप से विधानसभा या ओवरहाल के बाद, वैक्यूम पूरी तरह से नहीं है; जब रेफ्रिजरेंट को चार्ज किया जाता है या प्रशीतन तेल को जोड़ा जाता है, तो हवा को सिस्टम में लाया जाता है, या जब सिस्टम नकारात्मक दबाव में काम कर रहा होता है, तो हवा को तंग स्थानों के माध्यम से मिलाया जाता है। सर्द हवा में प्रवेश करने के बाद, इसमें एक निश्चित दबाव होता है, और सर्द पर एक निश्चित दबाव भी होता है। एक बंद कंटेनर में, कुल गैस दबाव आंशिक दबावों के योग के बराबर है, इसलिए उच्च और निम्न दबाव गेज रीडिंग सामान्य से अधिक है।
3. Treatment method: 1) Release refrigerant (release slowly from low pressure side with pressure gauge). 2) Check the cleanliness of the compressor oil. 3) Refill the refrigerant after vacuuming.
Fourth, & quot;ice blockage & quot; appears in the refrigeration system
1. Failure phenomenon: The refrigeration system periodically cools suddenly but not suddenly. During operation, the pointer on the low pressure side of the manifold pressure gauge often fluctuates between the negative pressure and the normal value.
2. Cause of failure: Moisture is mixed into the refrigerant in the refrigeration system. Because the water is incompatible with the refrigerant, when the refrigerant flows through the orifice of the expansion valve, the temperature drops suddenly. These are mixed in the refrigerant The water will easily form small particles of ice in the vicinity of the small hole of the throttle valve or around the valve pin hole, which is spherical or hemispherical. When the ice particles are condensed to a certain extent, the throttle channel is blocked and an ice jam fault is formed. . When ice blocking occurs due to icing, the refrigeration system cannot work properly, and the refrigeration effect is significantly reduced, even without refrigeration.
इस समय, कम दबाव गेज नकारात्मक दबाव दिखाई दिया, इसलिए बर्फ ब्लॉक का तापमान स्पष्ट रूप से उठाया गया था, बर्फ ब्लॉक के बर्फ के कण पानी में पिघल गए, जिससे बर्फ ब्लॉक घटना गायब हो गई, प्रशीतन प्रणाली ने सामान्य ऑपरेशन को फिर से शुरू किया, प्रशीतन अच्छा था, और निम्न दबाव का दबाव सामान्य पर लौट आया। थोड़ी देर के बाद, सिस्टम में बर्फ की रुकावट थी और सिस्टम ठीक से काम नहीं कर रहा था।
3. Treatment method: 1) Because the desiccant is in supersaturated state, it is necessary to replace the reservoir with desiccant and add 30ml of freezing oil. 2) Vacuum the system and add a specified amount of refrigerant.
पांचवां, गंदा रुकावट समस्या निवारण
1. Failure phenomenon: poor cooling effect or no cooling. When the air conditioning system is running, the readings of the high and low pressure gauges on the manifold pressure gauge are less than the normal value. (When the compressor speed is normal and the ambient temperature is around 35 ° C, the pressure on the high pressure gauge side is less than 9 kg / cm2, and the pressure on the low pressure side is Negative pressure), and there is frost or dew on the filter and capillary tube.
2. The cause of the failure: the dust in the refrigeration system adheres or adheres to the filter screen at the inlet end of the filter, or the interface between the capillary and the filter screen, so that a local throttling phenomenon is formed at this location, and the temperature drops rapidly, and condensation or condensation occurs Frost.
3. Treatment method: If there is frosting at the filter inlet, and the sound of intermittent airflow is heard, tap the filter body with a small wrench, the airflow sound changes, and the frost layer of the filter and capillary melts at the same time, which can be judged The filter inlet filter is clogged.
इस समय: cap केशिका निकालें, फिल्टर को साफ करें और सूखी उड़ा दें, और इसे फिर से स्थापित करें। या फ़िल्टर को हटा दें और खाली करें और रेफ्रिजरेंट को निर्धारित मात्रा में भरें।